The air conditioning demand of the world is largely fulfilled by vapor compression systems; however, these systems are also responsible for depleting ozone layer due to the nature of refrigerants. Desiccant cooling systems integrated with solar thermal energy technologies could be an attractive alternative with some performance enhancement techniques. In this study, transient seasonal performance investigation is performed for an innovative solar integrated desiccant cooling system that uses regenerative evaporative cooler known as solar assisted desiccant integrated Maisotsenko cycle cooler for better cooling performance. Furthermore, transient annual performance analysis of solar system for meeting thermal energy requirement for regenerating the desiccant wheel in summer season and handling heating load of the building in winter season is also carried out with three different solar thermal collector technologies for finding out more efficient technology. The key performance indicators in this study are useful energy gain, solar source efficiency, auxiliary energy sharing, coefficient of performance, and solar fraction. The results of the key performance parameters are reported as monthly average values. The proposed integrated system resulted to be very efficient with a maximum COP value of 1.13 in April when latent cooling loads are low and 0.78 in August when latent cooling loads are higher. The system's maximum cooling capacity is 24 kW in April corresponding to a sensible heat factor of 0.720. Furthermore, the regeneration temperature requirements ranged from 50 °C to 78 °C, respectively that makes it favorable to use low grade thermal energy through non concentrating solar thermal collectors. The regeneration thermal energy requirement for desiccant wheel fluctuates throughout the year, maximizing in August due to higher dehumidification requirements. The study also revealed that the evacuated tube collector technology is most suitable with average annual efficiency of around 36 %.

Original languageEnglish
Article number100634
JournalEnergy Conversion and Management: X
Volume23
DOIs
StatePublished - Jul 2024

Bibliographical note

Publisher Copyright:
© 2024 The Author(s)

Keywords

  • Desiccant cooling
  • Maisotsenko cycle cooler
  • Regenerative evaporative cooling
  • Solar air-conditioning
  • Solar thermal collectors
  • TRNSYS
  • Transient analysis

ASJC Scopus subject areas

  • Renewable Energy, Sustainability and the Environment
  • Nuclear Energy and Engineering
  • Fuel Technology
  • Energy Engineering and Power Technology