Abstract
This paper examined the performance of a thermo-electric air duct system (TE-AD), which employs the thermo-electric module (TEMs) inside an air duct for providing thermal comfort in Malaysian environment. Twenty human subjects were exposed to test room equipped with TE-AD system operating at six different input current supply from 2 A to 7 A. Both objective and subjective measurements were carried out. Results show that with the increment of input current supply to the TE-AD system, subject's thermal response related to indoor condition of test room shifted from warm to neutral. Optimum performance of the TE-AD system was obtained at the input current supply of 6 A, more than 80% of subjects responded in the range of ±1 and meets ASHARE standards of acceptability criteria. Further increase in input current supply deteriorates the cooling performance of the TE-AD system. Economic comparison of the TE-AD system with the existing air conditioning system shows that economic saving of US$ 127.34/year can be achieved with additional benefits of Freon free, convenient installation, no moving part and reliable operation.
Original language | English |
---|---|
Pages (from-to) | 1141-1155 |
Number of pages | 15 |
Journal | Applied Thermal Engineering |
Volume | 91 |
DOIs | |
State | Published - 5 Dec 2015 |
Bibliographical note
Publisher Copyright:© 2015 Published by Elsevier Ltd.
Keywords
- Economic analysis
- Thermal comfort
- Thermal sensation
- Thermoelectric air duct system
- Thermoelectric module
ASJC Scopus subject areas
- Energy Engineering and Power Technology
- Industrial and Manufacturing Engineering