Theoretical performance of HCFC123 as an alternative to CFC11

  • S. A.M. Said*
  • , Y. M. Suleiman
  • , B. Ismail
  • *Corresponding author for this work

Research output: Contribution to journalArticlepeer-review

3 Scopus citations

Abstract

Based on the thermodynamic properties of HCFC123 obtained by using a modified Benedict-Webb-Rubin (MBWR) equation of state fit to experimental measurements, the theoretical performance of HCFC123 has been assessed as an alternative to CFC11 by using standard refrigeration parameters, including pressure ratio, specific compressor displacement, coefficient of performance, and shaft power. This study indicates that a CFC11 compressor working with HCFC123 will have lower adiabatic head rise, efficiency and volume flow. This performance difference should not exclude HCFC123 as an alternative to CFC11 since most of the existing machines are oversized for a particular application and thus performance attained with HCFC123 could be adequate.

Original languageEnglish
Pages (from-to)205-208
Number of pages4
JournalEnergy
Volume20
Issue number3
DOIs
StatePublished - Mar 1995

Bibliographical note

Funding Information:
Acknowledgements-The authors would like to acknowledge support provided by King Fahd University of Petroleum and Minerals and Dammam College of Technology.

ASJC Scopus subject areas

  • Civil and Structural Engineering
  • Building and Construction
  • Pollution
  • Mechanical Engineering
  • Industrial and Manufacturing Engineering
  • Electrical and Electronic Engineering

Fingerprint

Dive into the research topics of 'Theoretical performance of HCFC123 as an alternative to CFC11'. Together they form a unique fingerprint.

Cite this