Abstract
The paper* summarizes the results of clean-fog tests conducted by eleven task force laboratories on a common suspension insulator, IEEE insulator.** The test series done according to a specific set of guidelines, show considerable dispersion in the fifty per cent flashover voltage between the laboratories. The significant parameters of the clean-fog method that influence the fifty per cent flashover voltage are discussed. More controls in testing are needed before the formalization of the clean-fog method as a standard contamination test for high voltage ac insulators can be made.
| Original language | English |
|---|---|
| Pages (from-to) | 604-613 |
| Number of pages | 10 |
| Journal | IEEE Transactions on Power Apparatus and Systems |
| Volume | PAS-102 |
| Issue number | 3 |
| DOIs | |
| State | Published - Mar 1983 |
ASJC Scopus subject areas
- Energy Engineering and Power Technology
- General Engineering
- Electrical and Electronic Engineering
Fingerprint
Dive into the research topics of 'The ac clean-fog test for contaminated insulators'. Together they form a unique fingerprint.Cite this