Abstract
The study presents the results of experimental investigation of finding out the limit concentrations of DBDS and sulfur mercaptan for safe and prolonged operation of power transformers in the local environmental conditions of Saudi Arabia. For experimental investigation of limit concentrations of DBDS and sulfur mercaptan, new oil free of sulfur compounds was acquired. Four specimens of this were spiked with 2.2, 3.9, 5.4 and 10.2 ppm of DBDS and another four with free sulfur mercaptan RSH concentrations of 0.00, 0.52, 1.07, 2.13, and 7.10 ppm. The covered conductor deposition (CCD) tests were performed in accordance with IEC 62535 method on all the specimens. The experimental results indicated that the concentration of DBDS should always be <5 ppm and sulfur mercaptan <1 ppm in the new oils before putting in to the service.
| Original language | English |
|---|---|
| Title of host publication | 34th Electrical Insulation Conference, EIC 2016 |
| Publisher | Institute of Electrical and Electronics Engineers Inc. |
| Pages | 37-39 |
| Number of pages | 3 |
| ISBN (Electronic) | 9781467387064 |
| DOIs | |
| State | Published - 22 Aug 2016 |
Publication series
| Name | 34th Electrical Insulation Conference, EIC 2016 |
|---|
Bibliographical note
Publisher Copyright:© 2016 IEEE.
Keywords
- DBDS
- corrosion
- sulfur
- sulfur mercaptan
- transformer oil
ASJC Scopus subject areas
- Polymers and Plastics
- Ceramics and Composites
- Electronic, Optical and Magnetic Materials
Fingerprint
Dive into the research topics of 'Study of limit concentrations of DBDS and sulfur mercaptan in power transformers'. Together they form a unique fingerprint.Cite this