Abstract
This work aimed to study the influence of contamination profiles and humidity on flashover electrical characteristics of polluted insulators. Firstly, the flashover tests on cap and pin glass insulators under four pollution levels represented by salinity were conducted. Eight artificial contamination profiles based on the solid layer method have been modeled for the selected insulators. The numerical analysis has been used to determine the insulator electrical characteristics such as potential, electric field, and power dissipation under proposed contamination profiles using finite element methods (FEM). Next, the power dissipation has been simulated with consideration of thermal stress propagation in locations with high power. Finally, flashover voltage gradient tests have been conducted under various humidity and contamination profiles. The values of the flashover voltage gradient due to pollution were determined as the percentage of the value of the flashover voltage gradient in the clean condition which was identified as the reference point. The numerical model indicated that the initiation of arc generally occurs at area in which the electric field and power dissipation is maximum. It was also observed from experimental results that the flashover voltage gradient under different contamination profiles has different values depends on the location and dimension of the pollution region.
| Original language | English |
|---|---|
| Pages (from-to) | 37800-37812 |
| Number of pages | 13 |
| Journal | IEEE Access |
| Volume | 9 |
| DOIs | |
| State | Published - 2021 |
| Externally published | Yes |
Bibliographical note
Publisher Copyright:© 2021 Institute of Electrical and Electronics Engineers Inc.. All rights reserved.
Keywords
- Contamination profiles
- Finite element method (FEM)
- Flashover voltage gradient
- Numerical model
- Polluted insulators
- Power dissipation
ASJC Scopus subject areas
- General Computer Science
- General Materials Science
- General Engineering