Performance improvement of a hybrid air conditioning system using the indirect evaporative cooler with internal baffles as a pre-cooling unit

Research output: Contribution to journalArticlepeer-review

38 Scopus citations

Abstract

In the present paper, the effects of the indirect evaporative cooler with internal baffle on the performance of the hybrid air conditioning system are numerically investigated. The hybrid air conditioning system contains two indirect evaporative coolers with internal baffle, one is utilized to pre-cool the air inlet to the desiccant wheel and the other is utilized to pre-cool the supply air inlet to the room. The effects of the inlet conditions of the process and reactivation air and working air ratio on the thermal performance of the hybrid air conditioning system have been analyzed. The results of this study show that in the hybrid air conditioning system for using the indirect evaporative cooler with internal baffle as a pre-cooling unit, the supply air temperature reduced by 21% and the coefficient of performance improved by 71% as compared to previous designs of the hybrid air conditioning system at the same inlet conditions. For increasing process air inlet temperature from 25 °C to 45 °C, supply air temperature increases from 12.7 °C to 14.2 °C, thermal COP increases from 1.87 to 2.84, and supply air relative humidity increases from 76.7% to 77.4%. Also, for increasing the reactivation air inlet temperature from 70 °C to 110 °C, supply air temperature dropped from 15.9 °C to 10.9 °C, supply air relative humidity dropped from 82.7% to 71.8%, and thermal COP dropped from 4.5 to 1.7. The recommended optimal air working ratio in the indirect evaporative cooler with internal baffle should be 0.15.

Original languageEnglish
Pages (from-to)395-403
Number of pages9
JournalAlexandria Engineering Journal
Volume56
Issue number4
DOIs
StatePublished - Dec 2017
Externally publishedYes

Bibliographical note

Publisher Copyright:
© 2017 Faculty of Engineering, Alexandria University

Keywords

  • Air conditioning
  • Desiccant material
  • Evaporative cooler
  • Internal baffles
  • Solar air collector

ASJC Scopus subject areas

  • General Engineering

Fingerprint

Dive into the research topics of 'Performance improvement of a hybrid air conditioning system using the indirect evaporative cooler with internal baffles as a pre-cooling unit'. Together they form a unique fingerprint.