Performance-based fire safety evacuation of an auditorium facility using a theoretical calculation method

Abubakar S. Mahmoud, Muizz O. Sanni-Anibire, Mohammad A. Hassanain*

*Corresponding author for this work

Research output: Contribution to journalArticlepeer-review

5 Scopus citations

Abstract

Purpose: The purpose of this paper is to present the findings of a theoretical calculation for the emergency evacuation of an auditorium facility managed by a university in Saudi Arabia. Design/methodology/approach: The authors reviewed the published literature to identify the sources of fire incidence, guidelines for means of escape in assembly occupancies and human behavior in fire emergencies. The theoretical method of the SFPE handbook to estimate the required evacuation time was subsequently applied to a case study of an auditorium facility managed by a university located in Saudi Arabia. Finally, the authors developed recommendations for the performance-based fire safety evacuation of the auditorium facility under review. Findings: The study showed that a total of 6 minutes 39 seconds is needed to evacuate the whole auditorium. However, reviewed literature for assembly occupancies requires between 4 minutes 30 seconds and 6 minutes 24 seconds for total evacuation. Though, the calculated evacuation time is close to generally acceptable limits. It was noted that overcrowding and bottlenecks may be formed in some of the exit routes. Originality/value: This paper will stimulate and increase research and industry concern for performance-based design of assembly-type facilities. This will be of significant value to designers, engineers, facilities managers, and owners in ensuring the safety of occupants in assembly-type facilities.

Original languageEnglish
Pages (from-to)124-138
Number of pages15
JournalInternational Journal of Building Pathology and Adaptation
Volume35
Issue number2
DOIs
StatePublished - 2017

Bibliographical note

Publisher Copyright:
© 2017, © Emerald Publishing Limited.

Keywords

  • Auditorium
  • Building code
  • Escape
  • Evacuation time
  • Fire safety

ASJC Scopus subject areas

  • Civil and Structural Engineering
  • Building and Construction