Performance analysis of an ejector cooling system with a conventional chilled water system

Syed A. Tirmizi, Osman K. Siddiqui, P. Gandhidasan, Syed M. Zubair*

*Corresponding author for this work

Research output: Contribution to journalArticlepeer-review

14 Scopus citations

Abstract

The central chilled water system servicing one of the academic buildings at the KFUPM campus located in Dhahran has been modeled numerically to combine with the ejector cooling system. This ejector system cools the water which is in turn utilized to cool the refrigerant in the chiller condenser and hence, the function of the cooling tower in a conventional chilled water system is eliminated by an ejector cooling system. By replacing the cooling tower of the chilled water system with an ejector cooling system, constant water inlet temperature for the chiller condenser is assured, regardless of the ambient relative humidity and this effect is analyzed in detail. Results indicate that this combined system is quite advantageous at conditions of high ambient relative humidity when the cooling capacity of the cooling tower is greatly diminished but the performance of the ejector cooling system remains unaffected.

Original languageEnglish
Pages (from-to)113-121
Number of pages9
JournalApplied Thermal Engineering
Volume66
Issue number1-2
DOIs
StatePublished - May 2014

Bibliographical note

Funding Information:
The authors acknowledge the support provided by King Fahd University of Petroleum and Minerals (KFUPM) for this research project.

Keywords

  • Chilled water system
  • Combined system
  • Ejector cooling
  • Performance characteristics

ASJC Scopus subject areas

  • Energy Engineering and Power Technology
  • Industrial and Manufacturing Engineering

Fingerprint

Dive into the research topics of 'Performance analysis of an ejector cooling system with a conventional chilled water system'. Together they form a unique fingerprint.

Cite this