New Approach for Monitoring Contamination Level on Outdoor Insulator Based on Harmonics Components of the Leakage Current

  • Ali Ahmed Salem
  • , Rahisham Abd Rahman
  • , Nor Akmal Mohd Jamail
  • , Nordiana Azlin Othman
  • , Irshad Ullah
  • , Hafisoh Binti Ahmad

Research output: Chapter in Book/Report/Conference proceedingConference contributionpeer-review

3 Scopus citations

Abstract

This paper presents a new and alternative approach to predict the severity of pollution by using components of leakage current LC on non-uniform polluted insulators. The LC harmonics components were measured using a new method based on wireless transmission. Laboratory tests were conducted on various pollution levels (0.05, 0.1, 0.15, 0.2, 0.25 and 0.3 mg/cm2) on 3 units string porcelain insulators under two level of voltage stress (0.23 kV/cm and 0.385kV/cm). The results of the test reported that the compare new indicator is the ratio of sum fifth and seventh frequency components to the third with the ratio of total harmonic distortion THD to odd harmonics components number n can be given as boundary for levels of pollution. According to the results of this test, the leakage current LC harmonics predictor K has a reasonable ability to determine the contamination level.

Original languageEnglish
Title of host publication13th International Conference on the Properties and Applications of Dielectric Materials
Subtitle of host publicationEmerging Dielectrics for Energy Sustainability, ICPADM 2021
PublisherInstitute of Electrical and Electronics Engineers Inc.
Pages418-421
Number of pages4
ISBN (Electronic)9781728182384
DOIs
StatePublished - 12 Jul 2021
Externally publishedYes

Publication series

NameProceedings of the IEEE International Conference on Properties and Applications of Dielectric Materials
Volume2021-July

Bibliographical note

Publisher Copyright:
© 2021 IEEE.

Keywords

  • Harmonics index
  • leakage current
  • porcelain insulators
  • Severity of pollution
  • THD

ASJC Scopus subject areas

  • Electronic, Optical and Magnetic Materials
  • Condensed Matter Physics
  • Materials Chemistry