Skip to main navigation Skip to search Skip to main content

Implementation of quadrature based RMS calculation on real-time power monitoring systems

Research output: Chapter in Book/Report/Conference proceedingConference contributionpeer-review

4 Scopus citations

Abstract

Accurate power system monitoring plays a vital role in detection of supply problems within the supply grid. Of all parameters being monitored, rms based measurements are used to detect various voltage based events within the system. IEEE and IEC based standards utilize full cycle instantaneous samples repeated every half a cycle for the calculation of rms. These measurements are not without limitations especially for short duration variations. This paper proposes 4-instantaneous sample points sampled at 90 degrees apart (quadrature based rms) to estimate rms and further detect voltage events in real-time. The proposed method is experimentally tested and applied for voltage events monitoring using Labview FPGA CompactRio platform. The results demonstrate the effectiveness of the proposed method for estimating the signal rms value with less number of samples.

Original languageEnglish
Title of host publication2013 IEEE Power and Energy Conference at Illinois, PECI 2013
Pages213-217
Number of pages5
DOIs
StatePublished - 2013

Publication series

Name2013 IEEE Power and Energy Conference at Illinois, PECI 2013

ASJC Scopus subject areas

  • Energy Engineering and Power Technology
  • Fuel Technology

Fingerprint

Dive into the research topics of 'Implementation of quadrature based RMS calculation on real-time power monitoring systems'. Together they form a unique fingerprint.

Cite this