Abstract
Majority of the high voltage transmission lines in Saudi Electricity Company-Eastern Region Branch (SEC-ERB) were constructed near coastal areas. The environmental conditions are unique due to combined desert and marine pollution with high ambient temperatures. Such conditions make insulator contamination flashovers the main concern to the electric utility. The insulators in this area are washed regularly to reduce their contamination flashovers even though the washing is very expensive. Therefore, it deemed necessary to search for an insulator of better pollution performance at low life cycle cost (LCC). As a part of comprehensive study, silicone rubber (SiR) insulators were installed in May 1996 on a 230 kV transmission line for trial of their performance in coastal area. Field and laboratory investigations were performed on SiR insulators. The test results provided better understanding of the SiR insulators aging phenomenon and confirmed their cost-effectiveness in polluted area.
| Original language | English |
|---|---|
| Title of host publication | Proceedings of the 2004 IEEE International Conference on Solid Dielectrics ICSD 2004 |
| Pages | 359-362 |
| Number of pages | 4 |
| State | Published - 2004 |
Publication series
| Name | Proceedings of the 2004 IEEE International Conference on Solid Dielectrics ICSD 2004 |
|---|---|
| Volume | 1 |
UN SDGs
This output contributes to the following UN Sustainable Development Goals (SDGs)
-
SDG 14 Life Below Water
ASJC Scopus subject areas
- General Engineering
Fingerprint
Dive into the research topics of 'Field and laboratory performance evaluation of SiR insulators in the Eastern coastal area of Saudi Arabia'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver