Abstract

In the line distance protection setting, the thyristor-controlled series capacitor type fault current limiter (TCSC-FCL) is usually treated as a reactor, ignoring the dynamic impedance characteristics, which may lead to operation failure/maloperation or slow response. To solving the problem above, TCSC-FCL dynamic impedance analysis model was established. Accounting for the bypass mode of TCSC-FCL in the first cycle, the time-varying characteristics of TCSC-FCL during the process from series compensation mode to limit dynamic mode was analyzed. Then the paper proposed the function expression of dynamic impedance characteristics of TCSC-FCL, and put forward distance protection setting strategy based on dynamic offset impedance circle, in order to eliminate the influence of TCSC-FCL dynamic impedance characteristics to the distance protection action. By establishing typical grid model including TCSC-FCL, the correctness of dynamic feature's function expression and the distance protection setting strategy are proved.

Original languageEnglish
Pages (from-to)2279-2289
Number of pages11
JournalZhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering
Volume37
Issue number8
DOIs
StatePublished - 20 Apr 2017
Externally publishedYes

Bibliographical note

Publisher Copyright:
© 2017 Chin. Soc. for Elec. Eng.

Keywords

  • Distance protection
  • Dynamic impedance process
  • Dynamic offset
  • Impedance circle
  • TCSC-FCL

ASJC Scopus subject areas

  • Electrical and Electronic Engineering

Fingerprint

Dive into the research topics of 'Distance Protection Setting Strategy Considering the Dynamic Impedance Process of TCSC-FCL'. Together they form a unique fingerprint.

Cite this