Abstract
With the increasing number of renewable generations, the prospects of long-distance bulk power transmission impels the expansion of point-to-point High Voltage Direct Current (HVDC) grid to an emerging Multi-terminal high-voltage Direct Current (MTDC) grid. TheDCgrid protection with faster selectivity enhances the operational continuity of the MTDC grid. Based on the reactor voltage gradient (RVG), this paper proposes a fast and reliable fault identification technique with precise discrimination of internal and external DC faults. Considering the voltage developed across the modular multilevel converter (MMC) reactor and DC terminal reactor, the RVG is formulated to characterise an internal and external DC fault. With a window of four RVG samples, the fault is detected and discriminated by the proposed main protection scheme amidst a period of five sampling intervals. Depending on the reactor current increment, a backup protection scheme is also proposed to enhance the protection reliability. The performance of the proposed scheme is validated in a four-terminal MTDC grid. The results under meaningful fault events show that the proposed scheme is capable to identify the DC fault within millisecond. Moreover, the evaluation of the protection sensitivity and robustness reveals that the proposed scheme is highly selective for a wide range of fault resistances and locations, higher sampling frequencies, and irrelevant transient events. Furthermore, the comparison results exhibit that the proposed RVG method improves the discrimination performance of the protection scheme and thereby, proves to be a better choice for future DC fault identification.
| Original language | English |
|---|---|
| Pages (from-to) | 115855-115867 |
| Number of pages | 13 |
| Journal | IEEE Access |
| Volume | 9 |
| DOIs | |
| State | Published - 2021 |
| Externally published | Yes |
Bibliographical note
Publisher Copyright:© 2021 Institute of Electrical and Electronics Engineers Inc.. All rights reserved.
UN SDGs
This output contributes to the following UN Sustainable Development Goals (SDGs)
-
SDG 7 Affordable and Clean Energy
Keywords
- Fault discrimination
- HVDC transmission
- fault identification
- fault resistance
- grid protection
- multi-terminal DC systems
- reactor voltage gradient
ASJC Scopus subject areas
- General Computer Science
- General Materials Science
- General Engineering