Skip to main navigation Skip to search Skip to main content

Condition assessment and repair strategy for seawater intake structure in Saudi Arabia

Research output: Chapter in Book/Report/Conference proceeding › Conference contribution › peer-review

Abstract

A reinforced concrete seawater intake structure is in service over the past three decades in a hypersaline marine environment in Saudi Arabia. Concrete spalling/delamination and corrosion of reinforcing steel were observed in the portion of the structure above the waterline. Condition assessment of the intake structure from outside and inside above and below the water line was conducted. Non-destructive and partially destructive investigations above and underwater, chloride and sulfate ion profiles, chloride ion permeability, water absorption and petrographic study of concrete cores was carried out. The overall structural rating of the structure is "Poor to Fair" with some zones being rated as "Serious". Reinforcement in the splash zone and above, in the walls, girders and beams, and top slab inside the seawater intake chamber are in an active state of corrosion after 32 years in service in harsh marine environment. A repair strategy was developed to enhance the service life of the structure.

Original languageEnglish
Title of host publicationConcrete Repair, Rehabilitation and Retrofitting III - Proceedings of the 3rd International Conference on Concrete Repair, Rehabilitation and Retrofitting, ICCRRR 2012
Pages590-595
Number of pages6
StatePublished - 2012

Publication series

NameConcrete Repair, Rehabilitation and Retrofitting III - Proceedings of the 3rd International Conference on Concrete Repair, Rehabilitation and Retrofitting, ICCRRR 2012

ASJC Scopus subject areas

  • Civil and Structural Engineering

Fingerprint

Dive into the research topics of 'Condition assessment and repair strategy for seawater intake structure in Saudi Arabia'. Together they form a unique fingerprint.

Cite this