Applications of LIBS for determination of ionic species (NaCl) in electrical cables for investigation of electrical breakdown

M. A. Gondal*, M. H. Shwehdi, A. A.I. Khalil

*Corresponding author for this work

Research output: Contribution to journalArticlepeer-review

17 Scopus citations

Abstract

The formation of water trees in high-voltage cables can wreak havoc to power systems. The water tree is produced within the high voltage cable insulator when impurities like sodium and magnesium present in the insulating material react with moist soil to form chlorides. This water tree causes electrical breakdown by short circuiting the metallic conductor and the earth. In this paper we use laser-induced breakdown spectroscopy (LIBS) to detect the potentially dangerous elements that form the water tree in the insulating cable. The LIBS system used for this work consists of the fundamental (1064 nm) of a Nd:YAG laser, four spectrometer modules that cover the visible and near-UV spectral ranges and an ICCD camera with proper delay and gating sequence. With this arrangement we were able to measure the elemental concentrations of trace metals present in the insulating cable. The concentrations measured with our LIBS system were counter checked by a standard technique like inductively coupled plasma (ICP) emission spectrometry. The maximum concentrations for ionic species such as Ba (455.40 nm), Ca (393.36 nm), Cr (267.71 nm), Fe (259.94 nm), Cl (542.3 nm), Mg (516.7 nm), Mn (257.61 nm), Na (589.59 nm) and Ti (334.18 nm) are 20.6, 43.2, 1.6, 148.4, 24.2, 22.1, 4.2, 39.56 and 4.35 ppm, respectively. The relative accuracy of our LIBS system for various elements as compared with the ICP method is in the range of 0.03-0.6 at 2.5% error confidence.

Original languageEnglish
Pages (from-to)915-922
Number of pages8
JournalApplied Physics B: Lasers and Optics
Volume105
Issue number4
DOIs
StatePublished - Dec 2011

ASJC Scopus subject areas

  • Physics and Astronomy (miscellaneous)
  • General Physics and Astronomy

Fingerprint

Dive into the research topics of 'Applications of LIBS for determination of ionic species (NaCl) in electrical cables for investigation of electrical breakdown'. Together they form a unique fingerprint.

Cite this