Application of frequency response analysis technique to detect transformer tap changer faults

Salem Mgammal Al-Ameri, Abdulaziz Almutairi*, Muhammad Saufi Kamarudin, Mohd Fairouz Mohd Yousof, Ahmed Abu-Siada, Mohamed Ibrahim Mosaad, Saeed Alyami

*Corresponding author for this work

Research output: Contribution to journalArticlepeer-review

14 Scopus citations

Abstract

Power transformers are located in the electrical transmission and distribution networks where different voltage levels are needed. The turn ratio of the low voltage and high voltage windings is mechanically controlled by an on-load tap changer or de-energized tap changer. As the tap changer is the transformer’s only moving part, it is highly susceptible to mechanical failure and aging degradation. While some diagnostic tools have been used to determine the mechanical condition of tap changer contacts, not much attention was given to use the frequency response analysis to diagnose the transformer’s tap changers’ mechanical integrity. This paper is taking one step forward into maturing the application of the frequency response analysis (FRA) technique to detect transformer tap changer faults. In this regard, two common tap changer faults are created, and experimental testing for four FRA test configurations is conducted. For a better understanding of the tap changer fault mechanism, an electrical equivalent circuit model is proposed and designed using Simulink. The simulation and implementation of the equivalent circuits using MATLABnR2018a.

Original languageEnglish
Article number3128
JournalApplied Sciences (Switzerland)
Volume11
Issue number7
DOIs
StatePublished - 1 Apr 2021
Externally publishedYes

Bibliographical note

Publisher Copyright:
© 2021 by the authors.

Keywords

  • Coking
  • Frequency response analysis
  • Pitting
  • Power transformer
  • Tap changer

ASJC Scopus subject areas

  • General Materials Science
  • Instrumentation
  • General Engineering
  • Process Chemistry and Technology
  • Computer Science Applications
  • Fluid Flow and Transfer Processes

Fingerprint

Dive into the research topics of 'Application of frequency response analysis technique to detect transformer tap changer faults'. Together they form a unique fingerprint.

Cite this