Skip to main navigation Skip to search Skip to main content

Analysis of overcurrent protective relaying as minimum adopted fault protection for small-scale hydropower plants

  • M. Noman
  • , I. Ullah
  • , M. A. Khan
  • , A. Qazi
  • , W. Farooq
  • , A. Saqr
  • , A. Elsheikh*
  • *Corresponding author for this work

Research output: Contribution to journalArticlepeer-review

37 Scopus citations

Abstract

In this research, the adoption of minimum fault protection and its coordination between local utility networks and embedded generation systems is analyzed using ETAP software. Overcurrent relay plays a significant role in the protection of the system, but when it comes to small-scale protection systems, the reliability of the system becomes cost-effective. Among the various growing renewable energy technologies, small hydropower is also used as an integrated distributed generation source, but problems related to false tripping usually occur due to interconnection with local utility networks. In this study initially, the load flow studies and short circuit analysis are performed for determining appropriate time and current gradients to suitably match the system's electrical parameters. Afterward, the adopted overcurrent relaying protection scheme is analyzed using protective device coordination analysis for precise tripping of relays in the intended sequential manner under various instigated fault instances over 11 kV utility networks. The proposed system is integrated with small-scale hydropower plants. This research addresses the potential gaps and rationalizes the minimum accepted protection scheme, which not only increases the reliability of the system but also makes it cost efficient which is required for fault clearing in small hydro-based distributed generation systems.

Original languageEnglish
Pages (from-to)4457-4470
Number of pages14
JournalInternational Journal of Environmental Science and Technology
Volume21
Issue number4
DOIs
StatePublished - Feb 2024
Externally publishedYes

Bibliographical note

Publisher Copyright:
© 2023, The Author(s) under exclusive licence to Iranian Society of Environmentalists (IRSEN) and Science and Research Branch, Islamic Azad University.

UN SDGs

This output contributes to the following UN Sustainable Development Goals (SDGs)

  1. SDG 7 - Affordable and Clean Energy
    SDG 7 Affordable and Clean Energy

Keywords

  • Distributed generation load flow
  • Hydro power plant
  • Overcurrent
  • Utility grid

ASJC Scopus subject areas

  • Environmental Engineering
  • Environmental Chemistry
  • General Agricultural and Biological Sciences

Fingerprint

Dive into the research topics of 'Analysis of overcurrent protective relaying as minimum adopted fault protection for small-scale hydropower plants'. Together they form a unique fingerprint.

Cite this