An improved non-dimensional model of wet-cooling towers

Research output: Contribution to journalArticlepeer-review

4 Scopus citations

Abstract

A general non-dimensional mathematical model of cooling towers is improved by including evaporation of water. The solution still consists of adjusting the assumed straight air-saturation line to the real air-saturation data, but a new constant (H) is added as well. Two solutions are proposed and the accuracy of each method is checked against data from the literature and also compared with the original solution. The first method shows a maximum decrease of 4.4 per cent in error, whereas in the second method, the maximum error was found to be 3.3 and 6.8 per cent when the inlet air was unsaturated and saturated, respectively.

Original languageEnglish
Pages (from-to)31-41
Number of pages11
JournalProceedings of the Institution of Mechanical Engineers, Part E: Journal of Process Mechanical Engineering
Volume220
Issue number1
DOIs
StatePublished - Feb 2006

Keywords

  • Cooling tower
  • Evaporation
  • Non-dimensional model

ASJC Scopus subject areas

  • Mechanical Engineering
  • Industrial and Manufacturing Engineering

Fingerprint

Dive into the research topics of 'An improved non-dimensional model of wet-cooling towers'. Together they form a unique fingerprint.

Cite this