A Microstructural Study of the Damage Sustained by Copper Shield Used in an Underground Medium-Voltage Cable

H. M. Tawancy*, Luai M. Alhems

*Corresponding author for this work

Research output: Contribution to journalArticlepeer-review

1 Scopus citations

Abstract

We show that a 3-mm-thick copper tape acting as metallic shield in an underground medium-voltage cable has been prematurely damaged by overheating. Detailed microstructural characterization has shown that the damage is characterized by: (a) formation of CuO on the copper surface as well as localized melting and perforation, (b) distortion and cracking of the outer protection jacket of polyvinyl chloride allowing the copper tape to come into contact with high sulfate-containing soil leading to deposition of CuSO4 on the copper surface, and (c) breakdown of the underlying layer of insulation shield. Most evidence suggests that overheating has been related to high return fault current exceeding the current-carrying capability of the copper tape used in the application. It is concluded that such a problem may be combated by using grounded objects with higher resistance to minimize the effect of return fault current and/or using copper shields with better current-carrying capability.

Original languageEnglish
Pages (from-to)73-81
Number of pages9
JournalMetallography, Microstructure, and Analysis
Volume6
Issue number1
DOIs
StatePublished - 1 Feb 2017

Bibliographical note

Publisher Copyright:
© 2016, Springer Science+Business Media New York and ASM International.

Keywords

  • Copper shield
  • Electron microscopy
  • Medium-voltage cable
  • Surface analysis

ASJC Scopus subject areas

  • Metals and Alloys

Fingerprint

Dive into the research topics of 'A Microstructural Study of the Damage Sustained by Copper Shield Used in an Underground Medium-Voltage Cable'. Together they form a unique fingerprint.

Cite this